BADA ATEX Non-Return Valve

Part No. BADA000018

An explosion involves not only the immediate processed material, but can also propagate to the rest of the process. This propagation can be avoided if the affected processed material is quickly isolated by a non-return valve.

The BADA non-return valve is designed to separate the filter from the plant. It is a simple and effective system that is easy to install, without electronics which requires no electrical connections, practically no maintenance and with very low pressure loss.

Our BADA non-return valve is an excellent ATEX certified Safety system for the compartmentalization of an explosion and is suitable for use in Ex zone 21 (ext.) and up to Ex zone 20 (int.).

£0
Shipping outside UK - Contact us
Please call for latest availability - 0800 032 0905
POA
£0.00 £0.00
£0.00 £0.00
Get in touchIs this the right product for you?Ask us a question

Product Details

Features

  • Economically suitable solution for security against an explosion
  • Completely mechanical requiring practically no maintenance
  • NO power consumption
  • Low pressure losses
  • High pressure resistance

Spare Parts

Purchasing spares,
made easy.

Service & Support For

Dust & Fume Extraction

Find out more

Technical Specification

BADA ATEX Non-Return Valve
Diameters Ø 200 up to Ø1000
Conformity according to EN 16447 2014 NFPA 69 Regulations
Certification Number FTZU 18 ATEX 0141 X
FTZU 16 ATEX Q 002
ATEX norm 114 2014/34/EC
Exterior zone certification 21-22
Interior zone certification 20-21-22
Level of protection St1 (organic & nonmetallic) up to 200 bar m/s
Kst max. 200 bar.m.s-1
Pred. max. 0.5 bar
Maximum airspeed 30 m/s
Use Indoors or outdoors
Min. / Max installation distance from filter Ø200: 2m to 7m
Ø200 - 400: 3m to 7m
Ø450 - 1000: 4m to 7m
Max. dust concentration in duct 400 g;m-3
Temperature range -20°C to +40°C.

Only to be used in horizontal ducting.